cleanroom ceilings: clip-in, bandraster or sandwich.
In a cleanroom the ceiling is a working surface as much as the floor is: the filtered air enters through it, the lighting sits in it, and it is cleaned with the same agents as the walls. That is why the ceiling is decided at the start of a project, not at the end. This guide sets out what a cleanroom ceiling has to deliver, how clip-in, bandraster and sandwich systems differ, what goes into the ceiling in filter units and lighting, and how it is serviced and changed later.
what a cleanroom ceiling has to deliver
The ceiling is the only cleanroom surface that supplies air, carries the lighting and has to be cleaned all at once, which is why it is decided before the walls. The requirements that follow are always the same: a smooth, non-porous surface with no open joints, a coved or profiled transition to the wall, joints that can be sealed, and openings for filter units and luminaires that stay flush with the surface.
ISO 14644-1 classifies cleanrooms by the concentration of airborne particles, from class ISO 1, the strictest, to class ISO 9; industrial and laboratory work usually calls for a class between ISO 5 and ISO 8, where ISO 5 corresponds to the former Class 100. The class is not a property of a panel but of the whole system: air changes, filter quality, the pressure cascade between zones and the gowning discipline of the people working inside.
Our cleanroom systems cover classes ISO 5 to ISO 8 (Class 100 to Class 100 000), with HEPA H14 filters as standard and ULPA U17 as an option, in line with ISO 14644-1 and GMP EU Annex 1, with validation documentation. The required class has to be known before a ceiling system is chosen, because it determines how many filter fields the ceiling carries and how tightly the joints are sealed.
- Smooth, non-porous surface with no open joints, resistant to cleaning agents.
- Sealed joints and a coved or profiled ceiling to wall transition.
- Filter units and luminaires flush with the ceiling, sealed around the perimeter.
- Classes ISO 5 to ISO 8, HEPA H14 as standard, ULPA U17 as an option.
- In line with ISO 14644-1 and GMP EU Annex 1, with validation documentation.

The ceiling is the only cleanroom surface that supplies air, carries the lighting and has to be cleaned all at once, which is why it is decided before the walls.
three ceiling systems: clip-in, bandraster and sandwich
Depending on project requirements we use three ceiling systems: clip-in, bandraster and sandwich. All three give a closed, cleanable surface and combine easily with each other, so one room can carry a sandwich ceiling over the technically settled part and a bandraster grid over the line that keeps changing.
A clip-in ceiling is made of panels that clip into a load-bearing substructure and come out from below. The surface stays almost unbroken and a single field opens without touching its neighbours, which suits a room where the ceiling has to look calm and is still opened occasionally.
A bandraster ceiling is carried by a profile grid, with fields sitting between its bands: blank panel, filter unit, luminaire. The band takes the load and the sealing, so a field is swapped without reworking the grid, which is the logic rooms with a changing process ask for. A sandwich ceiling is a self-supporting composite panel, two metal skins with an insulating core, mineral or PIR; it has the fewest joints and the most solid surface, but every change means work on the panel itself.
- Clip-in: the panel comes out from below, the surface stays calm.
- Bandraster: the profile grid carries, the fields are swapped one at a time.
- Sandwich: self-supporting panel, fewest joints, later changes cost more.
- All three systems combine zone by zone in the same room.
what goes into the ceiling: filter units, lighting and services
A cleanroom ceiling is not a cover but an air distributor: the filter fields in it make the whole ceiling work as an even top-down supply of clean air. At class ISO 5 and stricter a unidirectional, laminar flow is required, so the filter area takes up a large share of the ceiling; at ISO 7 and ISO 8 a mixed flow with enough air changes per hour is sufficient, so there are fewer fields and their layout follows the process underneath.
The cleanroom kits in our programme arrive with the fan filter unit and the ceiling luminaire already built in, so the field layout is not improvised on site. Luminaires sit flush with the ceiling and are sealed around the perimeter, and the same goes for sensors and monitoring points; anything hanging below the ceiling plane becomes a place where particles gather and work at every clean.
Services run enclosed, inside the profiles or above the ceiling plane, and break through it only at sealed penetrations. If a technical level above the ceiling is planned, it enters the design at the start, because it sets the clear height of the room and the way the ceiling will be serviced.
- Filter fields with HEPA H14, ULPA U17 as an option.
- ISO 5 and stricter: unidirectional flow, a larger filter area.
- ISO 7 and ISO 8: mixed flow, fewer filter fields.
- Fan filter unit and ceiling luminaire already built into the kit.
- Services enclosed, ceiling penetrations sealed.

sealing, silicone and cleaning
Joints between panels are sealed with elastic gaskets or sealant, depending on the class required, and the transition to the wall is coved or made with a dedicated corner profile so a particle has nowhere to settle. Every unsealed joint and every crack is a point of ingress and a point an inspector looks at. The advantage of a modular system is that the sealing quality is repeatable and does not depend on the skill of an individual trade on site.
Silicone is a question of its own. It travels: it spreads across surfaces, transfers on contact and is hard to remove once it has smeared. In electronics it interferes with bonding and coating, in pharmaceutical production it is a contaminant, so our cleanroom kits and self-build cabins carry silicone-free materials in the specification. If your process does not tolerate silicone, ask that question about the ceiling too, not only about the walls.
The ceiling is washed with the same agents as the walls, so the panel has to be chemically resistant and free of pores. Doors into a cleanroom ship with an interlock system and EPDM sealing, because the pressure cascade fails at the openings, not in the middle of a panel.
- Elastic gaskets or sealant, according to the ISO class required.
- Coved or profiled ceiling to wall transition.
- Silicone-free materials in the kit and self-build cabin specification.
- Doors: interlock system and EPDM sealing.

service: from the room or from above the ceiling
Filters are replaced, a luminaire fails, a sensor is calibrated. The only question is where they are reached from, and that is a design decision, not a site decision. If they are reached from below, a field is opened inside the clean space, so cleaning and re-checking that area follow the work. If there is a technical level above the ceiling, the service happens outside the classified space and production stops for less time.
A technical level above the ceiling needs clear height and a load-bearing substructure, which an existing hall does not always offer. Where it does not, a bandraster grid helps, because a single field is swapped without touching the rest of the ceiling, which also keeps the area that has to be cleaned again small.
It is worth knowing in advance how often the ceiling will be opened. A process with frequent format changes opens it several times a year, and then access from below in a clip-in or bandraster build works out cheaper than the most solid sandwich ceiling, which is built once and disturbed reluctantly.
- Access from below: work inside the clean space, then cleaning and a re-check.
- Technical level above: service outside the classified space.
- Bandraster: a smaller area to clean again.
- Service frequency drives the choice of system, not the other way round.
grid, changes and what to send for a quote
A modular structure with a flexible grid and wall connections means the field layout is drawn for the room as it is, not for the catalogue. Columns, beams and existing services enter the plan as given conditions rather than obstacles. When the process changes, fields are swapped and the grid is extended, and the class is kept without demolition.
Pre-assembled cladding arrives prepared and is fixed on site, with no wet trades and no drying time; our programme states a regional installation of three weeks, while validation is a separate phase whose duration depends on the certification scheme.
For a quote, send us the floor plan or the room dimensions, the clear height and what sits above the ceiling, the ISO class required and a short note on the process: what is done in the room, how many people enter and how often the ceiling is opened. With that we come back with a proposal for the ceiling system, the filter field layout and the lighting.

frequently asked questions
A smooth, non-porous surface with no open joints that is washed with the same agents as the walls, sealed joints, a coved or profiled transition to the wall, and filter units and luminaires flush with the surface and sealed around the perimeter. Above all that sits the class required by ISO 14644-1: it determines how many filter fields the ceiling carries and how tightly the joints are sealed.
It comes down to how often the ceiling is opened and what sits in it. Clip-in suits a room where the surface has to stay calm while a field is still taken out from below now and then. Bandraster is the choice where the process changes, because the profile grid carries the load and fields are swapped one at a time. Sandwich gives the fewest joints and the most solid surface where the ceiling is built once and rarely touched.
No. The class under ISO 14644-1 comes from air changes, filter quality, the pressure cascade between zones and gowning discipline, not from a single panel. The ceiling decides something else: whether that class can be held, because most of the supply air enters through it and pressure is lost at its joints.
In the filter fields of the ceiling itself, so the whole surface works as an even top-down air supply; HEPA H14 is the standard and ULPA U17 is an option. They are changed from below, inside the room, or from a technical level above the ceiling where one is provided. The first way means cleaning and re-checking that area after the work, the second never enters the classified space.
Yes. Clip-in, bandraster and sandwich combine easily with each other, so a sandwich ceiling can go over a settled zone and a bandraster grid over the line that keeps changing. That way flexibility is paid for only where it is actually needed.
The floor plan or room dimensions, the clear height and what sits above the ceiling, the ISO class required and a short description of the process: what is done, how many people enter, how often the ceiling is opened. With that we return a proposal for the ceiling system, the filter field layout and the lighting; without it only a price range is possible.
contact
Let's prepare your trade-fair project.
Tell us what you need. We will prepare a technical proposal aligned with your space, deadline and system.
- call
- +386 590 56 301
- visit
- Gerbičeva ulica 110
1000 Ljubljana
inquiry
Send us the basic information about your project. For a faster reply, include the fair location, the size of the exhibition space, the timeline and the desired system.
response time:We respond to inquiries within one business day, with a concept design and a ballpark quote.
